Skip to product information
1 of 4

Pixsys

Pixsys Signal Converter RTD/Thermocouples 2000.35.015

Pixsys Signal Converter RTD/Thermocouples 2000.35.015

Regular price $108.90
Regular price Sale price $108.90
Sale Sold out
Tax included.

This temperature transmitter for DIN/B head converts a signal acquired via PT100, PT1000, Ni100 probes or thermocouple into a  current signal for 4..20 mA loop (2-wire technology).
A version with galvanic isolation is also available (code 2000.35.015).

Unique features is the programming via NFC technology, not requiring the devices to be powered up. User can chose between a dedicated NFC programmer and RF-Programmer software on Pc or App MyPixsys on smartphone available on Play Store.

Product Datasheet

Part Number: 2000.35.015

 ORDERING CODES

2000.35.010

2000.35.015

Power supply

Loop Power (2 wires connection) operating range 6-32 Vdc

Analogue inputs

1 x selectable among Thermoresistances PT100, PT1000, Ni100 - 2/3/4 wires

 1 x selectable among Thermocouples K, S, R, J, T, N, B, E - Thermoresistances PT100, PT1000, Ni100 - 2/3/4 wires

Sampling/response time

300 mS / 600 mS

Rejection

50-60 Hz

 Output resolution

 2 μA

Max. transmission error

0,1% f.s o 0,2°C

Temperature coefficient

< 100 ppm

Cable resistance

Max 20Ω

Over-range output

f.s. + 5°C

Under-range output

f.s. - 5°C

Error output

Selectable between 21,5mA or 3,8mA

Current output protection

30 mA

View full details